Skip to main content
Speclore

Refrigerants Environment Properties

Reference data and engineering information about refrigerants environment properties for hvac systems applications.

RefrigerantsEnvironmentProperties

Overview

Engineering reference data for Refrigerants Environment Properties in HVAC systems.

Key Formulas

Sensible Heat

Q=m˙cpΔTQ = \dot{m} c_p \Delta T

Heat causing temperature change.

Latent Heat

Q=m˙hfgΔωQ = \dot{m} h_{fg} \Delta\omega

Heat causing moisture change.

COP (Cooling)

COP=Qc/WCOP = Q_c / W

Coefficient of performance.

Variables

SymbolDescriptionUnit
QQHeat transferW
m˙\dot{m}Mass flow ratekg/s
cpc_pSpecific heat of airJ/(kg·K)
ΔT\Delta TTemperature differenceK

Refrigerant Environmental Properties Data

27 rows
Common Refrigerants and their Environmental Properties. GWP values are relative to CO₂ (GWP = 1). ODP values are relative to R-11 (ODP = 1.0).
Refrigerant
Ozone Depletion Potential (ODP)
Global Warming Potential (GWP)
R-11 Trichlorofluoromethane14750
R-12 Dichlorodifluoromethane110900
R-13 B1 Bromotrifluoromethane10
R-22 Chlorodifluoromethane0.051810
R-32 Difluoromethane0675
R-113 Trichlorotrifluoroethane0.86130
R-114 Dichlorotetrafluoroethane19800
R-123 Dichlorotrifluoroethane0.0277
R-124 Chlorotetrafluoroethane0.02620
R-125 Pentafluoroethane03500
R-134a Tetrafluoroethane01430
R-143a Trifluoroethane04300
R-152a Difluoroethane0120
R-245a Pentafluoropropane0
R-401A (53% R-22, 34% R-124, 13% R-152a)0.0371100
R-401B (61% R-22, 28% R-124, 11% R-152a)0.041200
R-402A (38% R-22, 60% R-125, 2% R-290)0.022600
R-404A (44% R-125, 52% R-143a, R-134a)03922
R-407A (20% R-32, 40% R-125, 40% R-134a)02110
R-407C (23% R-32, 25% R-125, 52% R-134a)01774
R-454B (68.9% R-32, 31.1% R-1234yf)0466
R-502 (48.8% R-22, 51.2% R-115)0.2834657
R-507A (45% R-125, 55% R-143)03985
R-717 Ammonia - NH300
R-718 Water - H2O00
R-729 Air00
R-744 Carbon Dioxide - CO21

Source: engineeringtoolbox.com