Cooling Water Piping Systems

Reference data and engineering information about cooling water piping systems for hvac systems applications.

coolingwaterpipingsystems

Overview

Engineering reference data for Cooling Water Piping Systems in HVAC systems.

Key Formulas

Sensible Heat

Q=m˙cpΔTQ = \dot{m} c_p \Delta T

Heat causing temperature change.

Latent Heat

Q=m˙hfgΔωQ = \dot{m} h_{fg} \Delta\omega

Heat causing moisture change.

COP (Cooling)

COP=Qc/WCOP = Q_c / W

Coefficient of performance.

Variables

SymbolDescriptionUnit
QQHeat transferW
m˙\dot{m}Mass flow ratekg/s
cpc_pSpecific heat of airJ/(kg·K)
ΔT\Delta TTemperature differenceK

Pipe Performance Data

Below are reference tables for cooling water piping systems, showing maximum allowable flow, velocity, and pressure drop for different pipe sizes.

12 rows
Cooling Water - Main Pipes: Maximum allowable flow, velocity, and pressure drop.
Pipe Size(in)
Flow(US gpm)
Flow(liter/s)
Velocity(ft/s)
Velocity(m/s)
Pressure Drop(ftH₂O/100 ft)
Pressure Drop(Pa/100 m)
414093.51.12.221827
6380244.21.31.918877
8650414.21.31.413371
101100694.21.31.211700
1218001144.51.41.212093
1422001395.11.61.111208
1633002085.91.81.211405
1845002846.21.91.211503
2060003796.721.211503
24110006947.82.41.211700
301900011998.72.61.110913
370430.92.322712

Source: engineeringtoolbox.com

9 rows
Cooling Water - Lateral Pipes: Maximum allowable flow, velocity, and pressure drop.
Pipe Size(in)
Flow(US gpm)
Flow(liter/s)
Velocity(ft/s)
Velocity(m/s)
Pressure Drop(ftH₂O/100 ft)
Pressure Drop(Pa/100 m)
4200135.11.54.342179
6500325.61.73.231364
8900575.81.82.524383
101500956.11.92.120745
1224001516.82.12.120647
1431001967.22.22.120647
1645002847.92.42.120549
1860003798.32.5219565
310064.31.34.543949

Source: engineeringtoolbox.com

Interactive Charts

Cooling Tower Efficiency

Water - Absolute (Dynamic) Viscosity vs. Temperature and Pressure