Skip to main content
Speclore

Feedwater Chemistry Limits

Reference data and engineering information about feedwater chemistry limits for miscellaneous applications.

feedwaterchemistrylimits

Overview

Engineering reference data for Feedwater Chemistry Limits in miscellaneous.

Key Formulas

Unit Conversion

y=xky = x \cdot k

Multiply by conversion factor.

Linear Interpolation

y=y1+(xx1)(y2y1)x2x1y = y_1 + \frac{(x - x_1)(y_2 - y_1)}{x_2 - x_1}

Estimate between two known points.

Percentage

p=partwhole×100%p = \frac{\text{part}}{\text{whole}} \times 100\%

Part as fraction of whole.

Variables

SymbolDescriptionUnit
xxInput value
yyOutput value
kkConversion factor

ABMA Chemistry Limits

7 rows
Maximum recommended chemistry limits for boiler feed water according to ABMA.
Boiler Operating Pressure (psig / bar)
Total Dissolved Solids - TDS(ppm)
Total Alkalinity(ppm)
Total Suspended Solids(ppm)
0 - 50 (0 - 3.5)2500500
50 - 300 (3.5 - 20)350070015
300 - 450 (20 - 30)300060010
450 - 600 (30 - 40)25005008
600 - 750 (40 - 50)10002003
750 - 900 (50 - 60)7501502
900 - 1000 (60 - 70)6251251

Source: ABMA / engineeringtoolbox.com

5 rows
Maximum allowable impurities in boiler water.
Chemical
Symbol
Maximum Concentration(ppm)
Sodium sulphiteNA2SO31
Sodium chlorideNaCl10
Sodium phosphateNA3PO425
Sodium sulphateNA2SO425
Silica oxideSiO20.2

Source: ABMA / engineeringtoolbox.com