Nema Starters
Reference data and engineering information about nema starters for miscellaneous applications.
Overview
Engineering reference data for Nema Starters in miscellaneous.
Key Formulas
Unit Conversion
Multiply by conversion factor.
Linear Interpolation
Estimate between two known points.
Percentage
Part as fraction of whole.
Variables
| Symbol | Description | Unit |
|---|---|---|
| Input value | — | |
| Output value | — | |
| Conversion factor | — |
Polyphase Motor Starters
The table below shows the maximum motor horsepower ratings for three-phase (polyphase) motors based on NEMA starter size, supply voltage, and starting method.
NEMA Size | Continuous Amps(A) | Full Voltage @ 200V(hp) | Full Voltage @ 230V(hp) | Full Voltage @ 460/575V(hp) | Part Winding @ 200V(hp) | Part Winding @ 230V(hp) | Part Winding @ 460/575V(hp) | Wye Delta @ 200V(hp) | Wye Delta @ 230V(hp) | Wye Delta @ 460/575V(hp) |
|---|---|---|---|---|---|---|---|---|---|---|
| 00 | 9 | 1.5 | 1.5 | 2 | ||||||
| 0 | 18 | 3 | 3 | 5 | ||||||
| 1 | 27 | 7.5 | 7.5 | 10 | 10 | 10 | 15 | 10 | 10 | 15 |
| 2 | 45 | 10 | 15 | 25 | 20 | 25 | 40 | 20 | 25 | 40 |
| 3 | 90 | 25 | 30 | 50 | 40 | 50 | 75 | 40 | 50 | 75 |
| 4 | 135 | 40 | 50 | 100 | 75 | 75 | 150 | 60 | 75 | 150 |
| 5 | 270 | 75 | 100 | 200 | 150 | 150 | 350 | 150 | 150 | 300 |
| 6 | 540 | 150 | 200 | 400 | 300 | 600 | 300 | 350 | 700 |
Source: engineeringtoolbox.com
Single-Phase Motor Starters
The table below lists the maximum motor horsepower ratings for single-phase motors using full voltage starting with two-pole contactors.
NEMA Size | 115 Volts(hp) | 230 Volts(hp) |
|---|---|---|
| 00 | 0.333 | 1 |
| 0 | 1 | 2 |
| 1 | 2 | 3 |
| 2 | 3 | 7.5 |
| 3 | 7.5 | 15 |
Source: engineeringtoolbox.com
Starter Selection Criteria
Selecting a NEMA starter is straightforward and requires only two motor specifications:
- Motor Horsepower (hp)
- Motor Voltage (V)
A key practical advantage of NEMA starters is the use of interchangeable heater elements. This feature makes them particularly suitable for projects where the final motor specifications may not be confirmed until the installation or startup phase.