Skip to main content
Speclore

Nema Starters

Reference data and engineering information about nema starters for miscellaneous applications.

nemastarters

Overview

Engineering reference data for Nema Starters in miscellaneous.

Key Formulas

Unit Conversion

y=xky = x \cdot k

Multiply by conversion factor.

Linear Interpolation

y=y1+(xx1)(y2y1)x2x1y = y_1 + \frac{(x - x_1)(y_2 - y_1)}{x_2 - x_1}

Estimate between two known points.

Percentage

p=partwhole×100%p = \frac{\text{part}}{\text{whole}} \times 100\%

Part as fraction of whole.

Variables

SymbolDescriptionUnit
xxInput value
yyOutput value
kkConversion factor

Polyphase Motor Starters

The table below shows the maximum motor horsepower ratings for three-phase (polyphase) motors based on NEMA starter size, supply voltage, and starting method.

8 rows
Maximum motor horsepower ratings for polyphase (three-phase) motors by NEMA starter size, voltage, and starting method.
NEMA Size
Continuous Amps(A)
Full Voltage @ 200V(hp)
Full Voltage @ 230V(hp)
Full Voltage @ 460/575V(hp)
Part Winding @ 200V(hp)
Part Winding @ 230V(hp)
Part Winding @ 460/575V(hp)
Wye Delta @ 200V(hp)
Wye Delta @ 230V(hp)
Wye Delta @ 460/575V(hp)
0091.51.52
018335
1277.57.510101015101015
245101525202540202540
390253050405075405075
4135405010075751506075150
527075100200150150350150150300
6540150200400300600300350700

Source: engineeringtoolbox.com

Single-Phase Motor Starters

The table below lists the maximum motor horsepower ratings for single-phase motors using full voltage starting with two-pole contactors.

5 rows
Maximum motor horsepower ratings for single-phase motors using full voltage starting.
NEMA Size
115 Volts(hp)
230 Volts(hp)
000.3331
012
123
237.5
37.515

Source: engineeringtoolbox.com

Starter Selection Criteria

Selecting a NEMA starter is straightforward and requires only two motor specifications:

  1. Motor Horsepower (hp)
  2. Motor Voltage (V)

A key practical advantage of NEMA starters is the use of interchangeable heater elements. This feature makes them particularly suitable for projects where the final motor specifications may not be confirmed until the installation or startup phase.

Interactive Charts

Electrical Motors - Shaft Power vs. Voltage and Current

Maximum motor horsepower ratings for single-phase motors using full voltage starting.

References