Support Spacing Pvc Pipings
Reference data and engineering information about support spacing pvc pipings for statics applications.
supportspacingpvcpipings
Overview
Engineering reference data for Support Spacing Pvc Pipings in statics.
Key Formulas
Equilibrium
Sum of forces and moments equals zero for a body in equilibrium.
Stress
Force per unit area.
Moment
Force × perpendicular distance.
Variables
| Symbol | Description | Unit |
|---|---|---|
| Force | N | |
| Area | m² | |
| Moment | N·m | |
| Distance | m |
8 rows
NPS (inches) | DN (mm)(mm) | Standard Steel Pipe(ft) | Fiberglass Pipe(ft) | PVC Pipe (Schedule 80)(ft) |
|---|---|---|---|---|
| 1 | 25 | 7 | 12 | 4.5 |
| 1 1/2 | 40 | 9 | 14 | 5 |
| 2 | 50 | 10 | 15 | 5 |
| 3 | 80 | 12 | 17 | 6 |
| 4 | 100 | 14 | 19 | 7.5 |
| 6 | 150 | 17 | 22 | 8.5 |
| 8 | 200 | 19 | 24 | 9 |
| 10 | 250 | 22 | 27 | 9.5 |
Source: engineeringtoolbox.com
Operating Conditions
The tabulated support spacing values are based on the following conditions:
- Fluid: Water with a specific gravity of 1.0
- Temperature: 60°F (15.56°C)
Unit Conversion Note: 1 foot (ft) = 0.3048 meters (m).