Transformer
Reference data and engineering information about transformer for electrical applications.
transformerCalculator
Overview
A transformer transfers electrical energy between circuits through electromagnetic induction. It can step voltage up or down while conserving power (ideally).
Formula
Calculator
Notes
- Results are approximate and should be verified for critical applications
- Input values should be within reasonable engineering ranges
Single Phase Transformer Full Load Current
For a single-phase transformer, the full load current can be calculated using:
where:
- = full load current (A)
- = transformer apparent power (kVA)
- = voltage (V)
Three Phase Transformer Full Load Current
For a three-phase transformer, the full load current is:
Single Phase Transformer Ratings
23 rows
Rating(kVA) | 120 V(A) | 240 V(A) | 480 V(A) |
|---|---|---|---|
| 0.05 | 0.42 | 0.21 | 0.1 |
| 0.075 | 0.63 | 0.31 | 0.16 |
| 0.1 | 0.83 | 0.42 | 0.21 |
| 0.15 | 1.25 | 0.63 | 0.31 |
| 0.25 | 2.08 | 1.04 | 0.52 |
| 0.5 | 4.17 | 2.08 | 1.04 |
| 0.75 | 6.25 | 3.13 | 1.56 |
| 1 | 8.33 | 4.17 | 2.08 |
| 1.5 | 12.5 | 6.25 | 3.13 |
| 2 | 16.7 | 8.33 | 4.17 |
| 3 | 25 | 12.5 | 6.3 |
| 5 | 41.7 | 20.8 | 10.4 |
| 7.5 | 62.5 | 31.3 | 15.6 |
| 10 | 83.3 | 41.7 | 20.8 |
| 15 | 125 | 62.5 | 31.3 |
| 25 | 208 | 104.2 | 52.1 |
| 37.5 | 313 | 156.3 | 78.1 |
| 50 | 417 | 208.3 | 104.2 |
| 75 | 625 | 313 | 156 |
| 100 | 833 | 417 | 208 |
| 167 | 1392 | 696 | 348 |
| 200 | 1667 | 833 | 417 |
| 250 | 2083 | 1042 | 521 |
Source: engineeringtoolbox.com
Three Phase Transformer Ratings
14 rows
Rating(kVA) | 240 V(A) | 480 V(A) |
|---|---|---|
| 3 | 7.2 | 3.6 |
| 6 | 14.4 | 7.2 |
| 9 | 21.7 | 10.8 |
| 15 | 36.1 | 18 |
| 22 | 53 | 26.5 |
| 30 | 72.2 | 36.1 |
| 45 | 108 | 54.1 |
| 75 | 180 | 90.2 |
| 112.5 | 271 | 135 |
| 150 | 361 | 180 |
| 225 | 541 | 271 |
| 300 | 722 | 361 |
| 500 | 1203 | 601 |
| 750 | 1806 | 903 |
Source: engineeringtoolbox.com