Skip to main content
Speclore

Voltage Drop

Reference data and engineering information about voltage drop for electrical applications.

voltagedropCalculator

Overview

Voltage drop occurs as electrical current flows through conductor resistance, reducing the voltage available at the load. The National Electrical Code (NEC) recommends limiting voltage drop to 3% on branch circuits and 5% total (feeder plus branch). Accurate voltage-drop calculations help select the correct conductor size and ensure equipment operates within its rated voltage range.

Key Formulas

Ohm's Law approach:

ΔV=I×R\Delta V = I \times R

where resistance of a conductor is:

R=ρ×2LAR = \frac{\rho \times 2L}{A}

The factor of 2 accounts for both the supply and return conductors in a single-phase circuit.

Circular-mils approach:

ΔV=KPLIA\Delta V = \frac{K \cdot P \cdot L \cdot I}{A}

This form uses specific resistivity K in Ω·circular-mils/ft and wire area A in circular mils, avoiding the need for separate resistivity conversion.

Simplified copper formula:

ΔV=fIL\Delta V = f \cdot I \cdot L

where f is a precomputed factor (volts per ampere per 1000 ft) from the conductor table below, I is load current in amperes, and L is one-way wire length in feet.

Variables

SymbolDescriptionUnits
ΔVVoltage dropV
ILoad currentA
RConductor resistanceΩ
ρMaterial resistivityΩ·mm²/m
LOne-way conductor lengthft or m
AConductor cross-sectional areacircular mils or mm²
KSpecific resistivityΩ·circular-mils/ft
PPhase constant (single-phase = 2, three-phase = 1.732)
fSimplified voltage-drop factorV/(A·1000 ft)

Specific Resistivity (K Values)

4 rows
Specific resistivity for common conductor materials
Material
K (77–121 °F)(Ω·cmil/ft)
K (122–167 °F)(Ω·cmil/ft)
Solid Copper1112
Stranded Copper1112
Solid Aluminum1820
Stranded Aluminum1920

Source: engineeringtoolbox.com

Calculator

Voltage Drop — Circular Mils Method

Unit Converter

Voltage Drop Unit Converter

Source Examples

Example - Voltage Drop: for a single-phase copper circuit, voltage drop is calculated from conductor resistance, current, and one-way length with the return path included by the phase constant. Example - Specific resistivity and Voltage Drop: use the material K value in ohm-circular-mils per foot with conductor area in circular mils to avoid mixing SI and AWG units.

Copper Conductor Voltage Drop Factors

14 rows
Factor f for simplified copper voltage drop: ΔV = f × I × L (per 1000 ft)
AWG Size
Metric(mm²)
Single-Phase f(V/(A·kft))
Three-Phase f(V/(A·kft))
142.080.4760.42
123.310.3130.26
105.260.1960.17
88.370.1250.11
613.30.08330.071
421.20.05380.046
233.60.03230.028
1/053.50.02690.023
2/067.40.02220.02
4/0107.20.01610.014
2501270.01470.013
3001520.01310.011
4002030.01150.009
5002530.01010.009

Source: engineeringtoolbox.com

Voltage Drop Factor vs Conductor Cross-Section

Restored Original Source Tables

The following tables are restored from the original source page to preserve the complete reference data.

Copper Conductor - Voltage Drop

19 rows
Copper Conductor - Voltage Drop
AWG
Metric mm2
Factor - f -
Factor - f -
Single-phase3-phase
142.080.4760.42
123.310.3130.26
105.260.1960.17
88.370.1250.11
613.30.08330.071
421.20.05380.046
30.04310.038
233.60.03230.028
142.40.03230.028
1/053.50.02690.023
2/067.40.02220.02
3/0850.0190.016
4/0107.20.01610.014
2500.01470.013
3000.01310.011
3500.01210.011
4000.01150.009
5000.01010.009

Source: engineeringtoolbox.com

Engineering Notes

  • Temperature matters. Conductor resistance rises with temperature. Use the higher K value for circuits operating above 121 °F (49 °C).
  • Parallel conductors. For parallel runs, divide the total current by the number of parallel paths and calculate each path separately.
  • NEC recommendations. The NEC (NFPA 70) suggests a maximum 3% voltage drop on branch circuits and 5% total (feeder plus branch combined).
  • Aluminum conductors. Aluminum has roughly 1.6× the resistivity of copper; the K values and factors above reflect this difference.
  • Conduit and skin effect. At higher frequencies or in ferromagnetic conduit, effective resistance increases. The formulas here assume DC or 60 Hz in non-ferrous raceways.
  • Simplified formula limits. The factor-based method is calibrated for copper at standard building-wire temperatures. For aluminum or elevated-temperature designs, use the circular-mils formula with the appropriate K value.

References