Awg 电线 gauge chart & standards
American 电线 gauge 标准 sizes, diameters, resistances 与 ampacities.
awgwiregauge
Overview
The American Wire Gauge (AWG) system is the standard for measuring wire sizes in North America. Smaller AWG numbers indicate larger wire diameters.
Key relationships:
- Every 6 gauge decrease doubles the wire diameter
- Every 3 gauge decrease doubles the cross-sectional area
- AWG 0000 (4/0) is the largest standard gauge (11.684 mm diameter)
AWG Wire Table
17 行
AWG | Diameter(mm) | Area(mm²) | Resistance(Ω/km) | Ampacity (60°C)(A) |
|---|---|---|---|---|
| 0 | 8.251 | 53.49 | 0.3224 | 150 |
| 1 | 7.348 | 42.41 | 0.4066 | 130 |
| 2 | 6.544 | 33.63 | 0.5127 | 115 |
| 4 | 5.189 | 21.15 | 0.8152 | 85 |
| 6 | 4.115 | 13.3 | 1.296 | 65 |
| 8 | 3.264 | 8.366 | 2.061 | 50 |
| 10 | 2.588 | 5.261 | 3.277 | 35 |
| 12 | 2.053 | 3.309 | 5.211 | 25 |
| 14 | 1.628 | 2.081 | 8.286 | 20 |
| 16 | 1.291 | 1.309 | 13.17 | 0 |
| 18 | 1.024 | 0.823 | 20.95 | 0 |
| 20 | 0.812 | 0.518 | 33.31 | 0 |
| 22 | 0.644 | 0.326 | 52.96 | 0 |
| 24 | 0.511 | 0.205 | 84.22 | 0 |
| 26 | 0.405 | 0.129 | 133.9 | 0 |
| 28 | 0.321 | 0.081 | 212.9 | 0 |
| 30 | 0.255 | 0.0509 | 338.6 | 0 |
来源: engineeringtoolbox.com / NEC
AWG Formulas
Wire diameter for a given AWG number :
Cross-sectional area:
Common Applications
| AWG Range | Typical Use |
|---|---|
| 0000–0 | Service entrance, feeders |
| 1–4 | Large appliances, sub-panels |
| 6–10 | Ranges, dryers, A/C units |
| 12–14 | General household circuits |
| 16–18 | Extension cords, fixtures |
| 20–26 | Electronics, low-voltage |
| 28–40 | Signal wire, coils |
Note: Ampacity values vary significantly based on insulation type, ambient temperature, conduit fill, and installation method. Always refer to NEC tables for actual design.